EPA/HEPA/ULPA Filter Series
Ultravee
V-Bank Minipleat Filter

INTRODUCTION
-
Extended media surface creates lower resistance to higher air flow which save energy consumption.
-
Large media area provides filters longer serving life and higher dust holding capacity.
​
APPLICATION
-
These filters can be function normally in area of repeated turbulent air flow, repeated fan shutdown, desert, and marine installation.
SPECIFICATION
​
Media
Glass fibre with hot-melt separator​
​
Efficiency
E10 (≥85%), E11 (≥95%), E12 (≥99.5%), H13 (≥99.95%),
H14 (≥99.995%), U15 (≥99.9995%)
​
Frame
Acrylonitrile Botadiene Styrene (ABS)​
​
Header
20mm Single header (SH) (Option 25mm)
​
Sealant
Polyurethane
​
Gasket
Air leaving side (ALS)​
​
Temperature
≤ 70°C
​
Humidity
≤ 90% RH
​
Rated Velocity
2.5 m/s
​
Recommended final pressure drop
≤ 400Pa (E10), ≤500Pa (H13, H14, U15)



Specification appearance and content are subject to change without prioir notice